Process Automation For Water Treatment With PLC



See Simulation :
Process Automation For Water Treatment

Process Automation For Water Treatment


Detail Process Automation For Water Treatment :

Process Automation For Water Treatment
Information on Drawing Numbers for Detail Process Automation :
1.Valve to the Source of Dirty Water
2. Valve to Get Water From Water Tank 2
3. Valve to Get Water From Water Tank 1
4. Water Pump
5. Water Purifier or Water Purification or other
6. Valve for the Water to Water Tank 1
7. Valve for the Water to Water Tank 2
8. Clean Water Sensor or PH Water or other for Water Tank 1
9. Water Level Sensor or Water Level Gauge or other for Water Tank 1
10. Water Tank 1
11. Water Tank 2
12. Water Level Sensor or Water Level Gauge or other for Water Tank 2
13. Clean Water Sensor or PH Water or other for Water Tank 2
14. Switch ON / OFF


Number Of Inputs and Output PLC applied :
1. Number Of Inputs PLC is 9 Input :
--- 1 Unit Input for Switch ON / OFF (No.14).
--- 1 Unit Input for OK (Good) from Clean Water Sensor in Water Tank 1 (No.08).
--- 1 Unit Input for NG (No Good) from Clean Water Sensor in Water Tank 1 (No.08).
--- 1 Unit Input for OK (Good) from Clean Water Sensor in Water Tank 2 (No.13).
--- 1 Unit Input for NG (No Good) from Clean Water Sensor in Water Tank 2 (No.13).
--- 1 Unit Input for FULL WATER from Water Level Sensor in Water Tank 1 (No.09).
--- 1 Unit Input for EMPTY WATER from Water Level Sensor in Water Tank 1 (No.09).
--- 1 Unit Input for FULL WATER from Water Level Sensor in Water Tank 2 (No.12).
--- 1 Unit Input for EMPTY WATER from Water Level Sensor in Water Tank 2 (No.12).
--- Total Number Of Inputs PLC is Minimum 9 Input Unit.


2. Number Of Output PLC is 6 Output :
--- 1 Unit Output for Valve to the Source of Dirty Water (No.01).
--- 1 Unit Output for Valve to Get Water From Water Tank 2 (No.02).
--- 1 Unit Output for Valve to Get Water From Water Tank 1 (No.03).
--- 1 Unit Output for Water Pump (No.04).
--- 1 Unit Output for Valve for the Water to Water Tank 1 (No.06).
--- 1 Unit Output for Valve for the Water to Water Tank 2 (No.07).
--- Total Number Of Outputs PLC is Minimum 6 Output Unit.


Sequence PLC Programming for Process Automation For Water Treatment :

Step 1 :
a. If Switch = ON Then Valve No.01 = ON And Pump No.04 = ON And Valve No.06 = ON.
b. If FULL WATER No.09 = ON Then Valve No.01 = OFF And Pump No.04 = OFF And Check Clean Water Sensor No.08.
c. If OK (Clean Water Sensor) No.08 = ON Then Finish Process.
d. If NG (Clean Water Sensor) No.08 = ON Then Next Process to Step 2.


Step 2 :
a. If NG (Clean Water Sensor) No.08 = ON And Switch = ON Then Valve No.01 = OFF And Valve No.03 = ON And Pump No.04 = ON And Valve No.06 = OFF And Valve No.07 = ON.
b. If FULL WATER No.12 = ON Or EMPTY WATER No.09 = ON Then Pump No.04 = OFF And Valve No.03 = OFF And Check Clean Water Sensor No.13.
c. If NG (Clean Water Sensor) No.13 = ON Then Valve No.01 = OFF And Valve No.02 = ON And Valve No.03 = OFF And Pump No.04 = ON And Valve No.06 = ON And Valve No.07 = OFF.
d. If FULL WATER No.09 = ON Or EMPTY WATER No.13 = ON Then Pump No.04 = OFF And Valve No.02 = OFF And Check Clean Water Sensor No.08.
e. If OK (Clean Water Sensor) No.08 = ON Then Finish Process.
f. If NG (Clean Water Sensor) No.08 = ON Then Next Process to Step 2.a.
h. Continuous Process until Clean Water = OK.
Download Simulation Process :
Process Automation For Water Treatment


Step 3 :
a. If Switch = OFF Then Process Automation Stop.


Can You make Program Ladder PLC ?

If Can't :

PLC Omron Programming for Process Automation For Water Treatment

PLC Mitsubishi Programming for Process Automation For Water Treatment

PLC Keyence Programming for Process Automation For Water Treatment

PLC Omron Programming for Process Automation For Water Treatment


PLC Type Series-C Omron , Name Input / Output PLC :

INPUT PLC :
0000 ; Switch ON / OFF (No.14).
0001 ; OK from Clean Water Sensor in Water Tank 1 (No.08).
0002 ; NG from Clean Water Sensor in Water Tank 1 (No.08).
0003 ; OK from Clean Water Sensor in Water Tank 2 (No.13).
0004 ; NG from Clean Water Sensor in Water Tank 2 (No.13).
0005 ; FULL from Water Level Sensor in Tank 1 (No.09).
0006 ; EMPTY from Water Level Sensor in Tank 1 (No.09).
0007 ; FULL from Water Level Sensor in Tank 2 (No.12).
0008 ; EMPTY from Water Level Sensor in Tank 2 (No.12).

OUTPUT PLC :
0500 ; Valve to the Source of Dirty Water (No.01).
0501 ; Valve to Get Water From Water Tank 2 (No.02).
0502 ; Valve to Get Water From Water Tank 1 (No.03).
0503 ; Water Pump (No.04).
0504 ; Valve for the Water to Water Tank 1 (No.06).
0505 ; Valve for the Water to Water Tank 2 (No.07).


Please Download Picture Programming Ladder PLC :

PLC Omron Programming for Process Automation For Water Treatment



Reading Ladder PLC Programming for Process Automation For Water Treatment :

Step 1 : Process 1
a.If 0000 = ON Then 1000 = Momentary ON ( Diff. Up).
b.If 0000 = ON And 1000 = ON And 1002 = OFF And 1003 = OFF Then 1001 = ON ( Hold ON ).
c.If 0000 = ON And 1001 = ON And 0005 = ON And 0001 = ON Then SET 1002 = ON ( Hold ON ).
d.If 0000 = ON And 1001 = ON And 0005 = ON And 0002 = ON Then SET 1003 = ON ( Hold ON ).
e.If 0000 = OFF Then RES 1002 = ON ( 1002 = OFF ) And RES 1003 = ON ( 1003 = OFF ).

Step 2 : Process 2 And 3
PROCESS 2 :
a.If 0000 = ON And 1003 = ON And 0002 = ON And 1005 = OFF And 1006 = OFF Then 1004 = ON ( Hold ON ).
b.If 0000 = ON And 1003 = ON And 1004 = ON And 0007 = ON Or 0006 = ON And 0003 = ON Then SET 1005 = ON ( Hold ON ).
c.If 0000 = ON And 1003 = ON And 1004 = ON And 0007 = ON Or 0006 = ON And 0004 = ON Then SET 1006 = ON ( Hold ON ).
PROCESS 3 :
d.If 0000 = ON And 1003 = ON And 1006 = ON And 0004 = ON And 1008 = OFF And 1009= OFF Then 1007 = ON ( Hold ON ).
e.If 0000 = ON And 1003 = ON And 1006 = ON And 1007 = ON And 0005 = ON Or 0008 = ON And 0001 = ON Then SET 1008 = ON ( Hold ON ).
f.If 0000 = ON And 1003 = ON And 1006 = ON And 1007 = ON And 0005 = ON Or 0008 = ON And 0002 = ON Then SET 1009 = ON ( Hold ON ).
g.If 0000 = OFF Then RES 1005 = ON ( 1005 = OFF ) And RES 1006 = ON ( 1006 = OFF ) And RES 1008 = ON ( 1008 = OFF ) And RES 1009 = ON ( 1009 = OFF ).

Step 3 : Output PLC
a.If 0000 = ON And 1001 = ON Then 0500 = ON.
b.If 0000 = ON And 1007 = ON Then 0501 = ON.
c.If 0000 = ON And 1004 = ON Then 0502 = ON.
d.If 0000 = ON And 1001 = ON Or 1004 = ON Or 1007 = ON Then 0503 = ON.
e.If 0000 = ON And 1001 = ON Or 1007 = ON Then 0504= ON.
f.If 0000 = ON And 1004 = ON Then 0505 = ON.

Please Download Programming for SYSWIN :
PLC Omron Programming for Process Automation For Water Treatment


See : Process Automation For Water Treatment With PLC