Ethernet IP for RSControlLogix 5000 Start Guide





The RETA-01 adapter module is required to support communications when using Ethernet IP to communicate between an RSLogix 5000 PLC and the PS200.

1. Install the RETA-01 fieldbus module in option slot 1 of PS200. Be sure to use the fixing screws for proper ground bonding. Module power and signal connections are automatically made.
RETA-01 adapter module
2. Connect the Ethernet cable (RJ-45 connector) to the RETA-01 module, connector X1. Standard CAT 5 UTP or STP cables can be used. Avoid parallel runs with power (e.g. motor) cables.
3. Power up the drive. The “Module Status” led should be green. If the network cable is connected to an active network, the “LINK/ACTIVITY” led should also be solid or blinking green. The “Network Status” led will be steady green if the DCS/PLC has an Ethernet connection open against the drive.
4. Enter the proper pass code into the PS200 and go to parameter group 30. Be sure parameter 30.01shows “fieldbus”. Change parameter 30.03 to “CSA2.8/3.0”. St Up parameter group 31. Once group parameters are entered you must use parameter 31.27 to refresh the module or the new parameters will not take affect. Another way to refresh the module is to cycle power.
5. Set up PumpSmart for the type of process control required. Be sure to define all parameters being written to via EthernetIP to “Fieldbus”. Example include:
12.01 START/STOP
12.11 SPEED OVERRIDE
12.13 SPEED OVERRIDE REF
16.01 SET / SET 2 SELECT
16.02 SETPOINT 1 SELECT
16.03 SETPOINT 2 SELECT
ETC.
EthernetIP to Fieldbus