The Node of WebAccess SCADA offers a serial interface to the Programmable PLC of Sharp New Satellite JW10 with the Computer Link.

Cabling and Wiring
There are 2 kinds of substantial connections to the PLC of Sharp JW10:
1. The Port of MMI, this is the technique tested for this manual.
2. 2-wire Communication Terminals of RS-422. This technique is not tested for this guide.

The Port of MMI
The Port of MMI is a 9-pin port of in front of the PLC. It is the technique tested for this guide. This is a PLC per com port (a one-to-one Link). This manual was experienced with a 9-pin to 9- cable pin labeled PC JW10/TP02. The Manual of Sharp User explains a wire from Sharp, the model is JW-12KC. It is a 9-pin to 25-pin cable.

2-wire Port of Communications
The Link of Computer can also be through the Port of Communication. This is a 2-wire, connection of RS-422A on the Model JW-1642K PLC Lower terminals. It is a multiple drop link, up to 63 PLCs per com port. This technique was not experienced for this guide. The JW-1624K Lower Terminals utilized for 2-wire RS-422 are marked SHLD, L1, and L2. The twisted pair of shielded is needed.

Settings of PLC
Port of MMI
The default settings (memory#226 = 00000000) are:
The Rate of Transfer = 19200
Address of PLC = 01
Length of Data = 7 bits
Bits Stop = 1
Parity = None
The subsequent settings of system memory are used to set Parity, Data Length, Stop Bit, and Rate of Transfer when using the MMI Port computer link mode.
Description: specifications of transfer
Memory Number System: #226
Format: D0,D1, D2,D3, D4, D5,D7,0,
Communications Port of 2-wire
The JW10 has a Communications port of two-wire for using the link of computer, remote IO or data link. This function is decided by memory of system #234:
#234 = 2 = Remote I/O Link
#234 = 1 = Data Link
#234 = 0 = Mode of Computer Link it is requisite by WebAccess.
System Memory#236 sets the specification Transfer for the Communications Port of 2-wire. The default settings (memory#236 = 00000000) are:
Length of Data = 7 bits
Bits Stop = 1
Parity = None
The Rate of Transfer = 19200
Address of PLC = 01
Number of System Memory: #236
Description: specifications of transfer
Format: D0,D1, D2,D3, D4, D5,D7,0,
System Memory#237 sets the Address of PLC: 001 to 077.